Anfield SPA Pressure Switch Installation Instructions - Adjusting The Set Point

Today we will introduce the most important part of Anfield pressure switch manual, how to adjust the set point.

Firstly, we need to understand some characteristics of Anfield pressure switches.

ANFIELD PRESSURE SWITCH OPERATING SPECIFICATIONS & CHARACTERISTICS

MODEL ADJUSTMENT RANGE (psi) AVERAGE DIFFERENTIAL PROOF PRESSURE (psi) ADJUSTMENT (psi per turn)
SPA - 1 3 - 7 6-20% of setting 350 1
SPA - 2 5 - 30 6-20% of setting 350 3
SPA - 3 25 - 150 6-20% of setting 350 25

ADJUSTING THE SET POINT:

(Default setting is the lowest setting within range)

Step 1: Insert a 5/64” or 2mm allen key into the adjustment screw opening. (Fig 3)

Step 2: Turn the screw clockwise to increase the set point or counter clockwise to decrease.

Step 3: The adjustment screw may be potted with silicone to prevent moisture ingress through the adjustment screw

Fig 3. Setting

Please note that pressure gauge or other pressure instrument is required to assist during the adjustment process.

If you have any questions during use, please feel free to contact us at any time.

CONTACT CLOSENSE

CLOSENSE TECHNOLOGY CO., LTD.

Closense company was founded in 2012, is a professional company specializing in the sales, application, and technology of industrial sensors. The company operates the brand Closense and distributes well-known sensor brands in Europe and America, such as Anfield in Canada, Sendx in Germany, GEMS in the United States, SETRA, Vector, and HUBA Control in Switzerland. With rich sales experience, The company provides customers with the most complex and important key components in the field of industrial control and measurement, such as pressure switches, pressure transmitters, differential pressure sensors, liquid level switches, flow sensors, and temperature sensors.